c) Modify the outlet piping by
making it larger or shortening
the length of pipe, thereby
reducing the effects of built-up
backpressure.
OVERSIZED VALVE
While most PRVs are protecting equipment for more than one relief event,
the size of the valve is based on the
scenario requiring the greatest relieving capacity. An example would be
when a PRV is sized for both fire and
blocked outlet scenarios. The fire sizing
requires significantly greater orifice
area than the blocked outlet sizing.
However, since the blocked outlet
scenario is more common and more likely
to occur, then the PRV will be potentially starved for capacity, causing the
valve to “chatter” (rapidly opening
and closing). Valve chatter, as well as
flow instability, could inevitably cause
valve damage such as premature
fatigue failure of the bellows, as well
as galling of guiding surfaces. In our
experience, a PRV should not be specified that has an actual orifice area
more than 3 to 5 times larger than the
required area.
Mitigation strategies for failure in
this scenario include:
a) Install multiple PRVs and stagger
the set pressure for each of the
scenarios. Ensure the small valve
is properly sized based on the low-
est required capacity relief sce-
nario.
HIGH INLET
PRESSURE DROP
When the length of pipe leading to the
inlet of the PRV causes an excessive
pressure drop to a level below its reseat
pressure, the valve will begin to oscillate open and closed, potentially leading
to chatter. This situation can lead to bellows failure caused by premature
fatigue. A bellows with this type of failure will typically have a horizontal
crack along its convolutions or a complete fracture.
Mitigation strategies in this case
include:
a) Use a pilot valve and remote
sense the pressure-pickup point,
locating the pickup directly on or
closer to the equipment under
protection. This will ensure the
valve function is based on the
pressure at the equipment and not
the inlet of the PRV.
b) Install a modulating pilot-operat-
ed valve that will open in propor-
tion to the upstream pressure and
be less susceptible to chatter from
inlet line losses.
c) Lower the set pressure of the
PRV, which will reduce the capac-
ity of the PRV. Keep in mind the
operating pressure and the typical
blow-down may not allow this.
d) Modify the inlet pipe to reduce
inlet line pressure losses.
e) Raise the blow-down ring, which
lengthens the blow-down time.
While it is difficult to quantify the
increase in blow-down, in general,
raising the ring will reduce chatter.
OPERATING TOO CLOSE
TO SET PRESSURE
Operating a system too close to the set
pressure of a PRV can cause a valve to
be in a state of simmer. When the valve
is between simmer and fully open, this
can be classified as “flutter.” Although
this state is neither open nor closed,
the disc of the valve will have a very
small oscillation and may cause galling
in the guiding surfaces, as well as
fatigue failure of the bellows. The
American Petroleum Institute recommends a 90% operating-to-set pressure
ratio.
Recommendations for mitigating
this type of failure include:
a) Reduce the operating pressure.
For the cases described in this article, we assumed that all calculations
have been reviewed by a qualified engineer. Prior to implementing any of these
recommendations, please consult an
applications engineering team to verify
acceptable mitigation strategies. VM
SEAN CROXFORD is business operations manager,
Farris Engineering Services. Reach him at
scroxford@curtisswright.com. Martin Joyce is
applications engineering manager, Farris
Engineering. Reach him at
mjoyce@curtisswright.com.